27 POWERLINE CARRIER DEVICE (X-10) HOUSE ID 0
Powerline Carrier devices require a House ID. This field identifies this
House ID to the control.
If Powerline Carrier devices are used, they are selected in field
*
80.
House ID is entered in following manner:
0 = A, 1 = B, 2 =C, 3 = D, 4 = E, 5 = F, 6 = G, 7 = H, 8 = I, 9 = J,
# + 10 = K, # + 11 = L, # + 12 = M, # + 13 = N, # + 14 = O, # + 15 = P.
*
28 PHONE MODULE ACCESS CODE 0 | 0
1-9 = first digit of access code
*
or # = second digit of access code (enter # +11 for "
*
", or # +12 for "#")
The use of a 4285 Phone Module (can be used in Partition 1 only)
requires a 2-digit code.
Example:
If desired access code is 7
*
, 7 is the first entry, and # + 11
(for
*
) is the second entry.
NOTE: A “0” in either digit disables the Phone Module.
*
29 OUTPUT TO LONG RANGE RADIO (No. 7720PLUS/7820) 0
If output to LRR is selected here, all messages that are programmed to
go to the primary telephone line receiver will also be sent to the 7720
PLUS or 7820 radio. These messages will always be in Contact ID
format (not affected by entry in field
*
48). The data line is supervised as
well as certain functions in the radio. If communication is lost or a
trouble develops, a message will be attempted to be sent via both radio
and telephone to the central station.
Note: Normal trouble restore report (
*
71) is sent on restore of the
condition.
Entry is first digit of Trouble Dialer Report; enter Trouble code 1–9,
B (# +11), C (# +12), D (# +13), E (# +14), or F (# +15). The 2nd digit of
Trouble Dialer Report is automatically the 2nd digit from field
*
60.
UL installations: must be 0 (Long Range Radio disabled)
Note: The Radio should be programmed for device address 3 on the
keypad lines.
*
31 SINGLE ALARM SOUNDING PER ZONE (per armed period) 0
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming period for a given zone.
UL installations: must be 0 (no limit)
*
32 FIRE SOUNDER TIMEOUT 0
0 = yes, fire sounder timeout after time programmed in field *33
1 = no fire sounder timeout; continue sounding until manually turned off
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .